Triconex 3301 Digital Input Module

TRICONEX Triple redundant fault-tolerant control system is introduced:Invensys TRICONEX system, completely follow IEC61508/61511 standard, adopt the most advanced TMR microprocessor hardware technology, mature and reliable TRISTATION 1131 triple redundant fault-tolerant control system of the software.

System of high reliability and high efficiency, is widely used in petrochemical, oil refining, petroleum, chemical, electric power, rail transportation, aerospace, nuclear industry and other industries, the device safety interlock system ESD, steam turbine, gas turbine control, compression pant of vibration control, offshore oil platform, internal heat monitoring protection (head), there are a wide range of aspects such as performance.

The Tricon system can be rackmounted or panel-mounted in an industry-standard NEMA enclosure as described on the next page. Cabinets can optionally be equipped with base and casters. Multiple cabinets can be bolted together on the sides, but sufficient clearance must be allowed to fully open their front and rear doors.

Category:

Description

Model Type
 Input module

Model Number

Triconex 3301


Manufacturer(s)
Triconex

Additional Information

Points                  32, commoned
Nominal input voltage         24 VDC
Operational voltage range      15–30 VDC
Absolute maximum input voltage   33 VDC
Absolute maximum reverse input voltage – 0.6 VDC
Input                    delay <10 ms, On to Off or Off to On TC = 6.4 ms, –3dB @ 25Hz Input impedance              >30 kΩ, without baseplate
≈3 kΩ, with baseplate
Input power                  0.2 W/pt, @ 24 VDC
0.5 W/pt, @ 33 VDC
Input threshold                0–5 VDC = Off region
6–14 VDC = transition region
15–30 VDC = On region
Diagnostic (loss of view)         Force-to-value diagnostic (FVD),
<2 ms/test Maximum input toggle rate to maintain diagnostic fault coverage           <20/sec FVD Off state glitch Duration                      <2 ms Magnitude                     ≈36% test voltage Output Impedance                 0–5 VDC,≈ 100 kΩ ADC scan time                  <1 ms for all 32 points Functional earth to protective earth isolation   500 VDC, minimum Functional earth to functional earth (logic ground) isolation                   800 VDC, minimum .

 

Brand

Triconex

Reviews

There are no reviews yet.